7 Installation
Installer reference guide
48
EBLQ+EDLQ011~016CAV3+W1 + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
Backup heater
type
Connections to
backup heater power
supply
Connections to
terminals
3kW 1~ 230V
(*3V)
L NL N
F1B
3kW 1~ 230V
(*9W)
6kW 1~ 230V
(*9W)
LL NN
F1B
1 2 3
4 5 6
X14M
6kW 3N~ 400V
(*9W)
9kW 3N~ 400V
(*9W)
F1B
L1 L2 L3
1 2 3
4 5 6
X14M
Special remark for fuses:
Special remark for terminals:
As mentioned on the table above, the connections on the terminals
X6M and X7M need to be changed to configure a backup heater.
Refer to the illustration below as a caution about handling the
terminals.
3 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
For more information on the backup heater types, and for
how to configure the backup heater, refer to the
"Configuration" chapter of the installation manual of the
outdoor unit.
During connection of the backup heater, miswiring is possible. To
detect possible miswiring on the *9W model, it is highly
recommended to measure the resistance value of the heater
elements. Depending on the different backup heater types, following
resistance values (see table below) should be measured. ALWAYS
measure the resistance on the contactor clamps K1M, K2M, and
K5M.
3kW
1~ 230V
6kW
1~ 230V
6kW
3N~
400V
9kW
3N~
400V
K1M/1 K5M/13 52.9Ω 52.9Ω
K1M/3 105.8Ω 105.8Ω 105.8Ω
K1M/5 158.7Ω 105.8Ω 105.8Ω
K1M/3 K1M/5 26.5Ω 52.9Ω 105.8Ω 105.8Ω
K2M/1 K5M/13 26.5Ω
K2M/3 52.9Ω 52.9Ω
K2M/5 52.9Ω 52.9Ω
K2M/3 K2M/5 52.9Ω 52.9Ω 52.9Ω 52.9Ω
K1M/5 K2M/1 132.3Ω
Example measure resistance between K1M/1 and K5M/13:
K1M K2MK2M
1 3 5 13
2 4 6 14
K5M
1 3 5 13
2 4 6 14
1 3 5 13
2 4 6 14
Ω
Ω
7.8.21 To connect the backup heater kit to the
control box
INFORMATION
Requires to be connected to control box
EKCB07CAV3.