8 Configuration
Installer reference guide
57
EBLQ+EDLQ011~016CAV3+W1 + EK(2)CB07CAV3 +
EKMBUHCA3V3+9W1
Daikin Altherma low temperature monobloc
4P522034-1 – 2018.01
# Code Description
[A.2.3.3] [6-04] BUH: step 2: Only applies to a two-step
backup heater (*9W). The capacity
difference between the second and first
step of the backup heater at nominal
voltage. Nominal value depends on the
backup heater configuration. Default:
0kW.
3kW, 1N~ 230V: 0kW
6kW, 1N~ 230V: 3kW (6kW-3kW)
6kW, 3N~ 400V: 3kW (6kW-3kW)
9kW, 3N~ 400V: 6kW (9kW-3kW)
Range: 0~10kW (in steps of 0.2kW)
8.2.5 Space heating/cooling control
The basic required settings in order to configure the space heating/
cooling of your system are described in this chapter. The weather-
dependent installer settings define the parameters for the weather-
dependent operation of the unit. When weather-dependent operation
is active, the water temperature is determined automatically
depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-
dependent operation, the user has the possibility to shift up or down
the target water temperature by a maximum of 5°C.
See the user reference guide and/or operation manual for more
details about this function.
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A LWT setpoint mode:
0 (Fixed)
The desired leaving water
temperature is:
NOT weather-dependent (i.e. does
NOT depend on the outdoor
ambient temperature)
fixed in time (i.e., NOT scheduled)
1 (Weather dep.) (default): The
desired leaving water temperature is:
weather-dependent (i.e. depends
on the outdoor ambient
temperature)
fixed in time (i.e., NOT scheduled)
continued >>
# Code Description
[A.3.1.1.1] N/A << continuation
2 (Fixed/scheduled): The desired
leaving water temperature is:
NOT weather-dependent (i.e.,
does NOT depend on the outdoor
ambient temperature)
according a schedule. The
scheduled actions consists of
desired shift actions, either preset
or custom.
Remark: This value can only be
set in leaving water temperature
control.
3 (WD/scheduled): The desired
leaving water temperature is:
weather-dependent (i.e., does
depend on the outdoor ambient
temperature)
according a schedule. The
scheduled actions consists of
desired leaving water
temperatures either preset or
custom.
Remark: This value can only be
set in leaving water temperature
control.
# Code Description
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
Set weather-dependent heating:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
: Target leaving water temperature
(main)
T
a
: Outdoor temperature
continued >>