9 | Electrical installation
Installer reference guide
119
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
Legend: see illustration below.
In case of preferential kWh rate power supply
30
31
S1S
X2M
X1M
1
3
4
2
3
X5M
L N
L N
c
1 2 3
1 2 3
b
a
a Interconnection cable (=main power supply)
b Normal kWh rate power supply
c Preferential power supply contact
2 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
If the system is connected to a preferential kWh rate power supply, a separate
normal kWh rate power supply is required. Change connector X6Y according to the
wiring diagram on the inside of the indoor unit.