7 | Unit installation
Installer reference guide
65
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
7 Make sure the gas boiler is fixed properly and well aligned with the indoor
unit.
7.5.2 To install the condensate trap
INFORMATION
The boiler is provided with a Ø25mm flexible pipe on the condensate trap.
Prerequisite: The boiler MUST be opened before installing the condensate trap.
1 Fit the flexible tube (accessory) to the condensate trap outlet.
2 Fill the condensate trap with water.
3 Slide the condensate trap as far as possible upwards onto the condensate
drain connector below the gas boiler.
4 Connect the flexible tube (where applicable with the overflow pipe from the
pressure relief valve) to the drain via an open connection.