10 | Configuration
Installer reference guide
141
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
d Shower (field supply)
e Inlet on boiler
f Recirculation thermistor (EKTH2) (field supply)
g Water supply
h Non-return valve (field supply)
In case of [E‑06]=1
Domestic hot water pump installed for…
Instant hot water Disinfection
c
f
b
a
g
c
b
a
d f
e g
a Indoor unit
b Tank
c Domestic hot water pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
f Shower (field supply)
g Cold water
INFORMATION
The correct domestic hot water default settings become only applicable when
domestic hot water operation is activated ([E‑05]=1).
Thermostats and external sensors
# Code Description
[A.2.2.4] [C-05] Contact type main
In external room thermostat control, the contact
type of the optional room thermostat or heat
pump convector for the main leaving water
temperature zone must be set.
1 (Thermo ON/OFF): The connected external
room thermostat or heat pump convector
sends the heating or cooling demand by the
same signal as it is connected to only 1 digital
input (preserved for the main leaving water
temperature zone) on the indoor unit (X2M/1).
Select this value in case of a connection to the
heat pump convector (FWXV).
2 (H/C request)(default): The connected
external room thermostat sends separate
heating and cooling demand and is therefore
connected to the 2 digital input (preserved for
the main leaving water temperature zone) on
the indoor unit (X2M/1 and 2). Select this value
in case of connection with the wired (EKRTWA)
or wireless (EKRTR1) room thermostat.