10 | Configuration
Installer reference guide
189
EVLQ05+08CA + EHYHBH05A + EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
Measured value at maximum
power
Adjustment values CO
2
(%) at minimum power
(front cover opened)
Natural gas 2H/2E
(G20, 20mbar)
Propane 3P (G31,
30/50/37mbar)
10.8 10.5±0.1
10.6 10.3±0.1
10.4 10.1±0.1
10.2 9.9±0.1
10.0 9.8±0.1
9.8 9.6±0.1
9.6 9.0±0.1
9.4 8.9±0.1
9.2 8.8±0.1
9.0 8.7±0.1
8.8 8.6±0.1
8.6 8.5±0.1
3 After measuring the CO
2
percentage and adjusting the setting, put the cover
cap and the sampling point back in their place. Make sure they are gastight.
4 Select High setting by simultaneously pressing and twice. Capital will
appear on the service display.
5 Measure the CO
2
percentage. If the CO
2
percentage still deviates from the
values in the table indicating the CO
2
percentage at maximum power, contact
your local dealer.
6 Press and simultaneously to exit the test program.
7 Put the front panel back in its place.