9 | Electrical installation
Installer reference guide
107
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
3 (Optional) Drain tube heater cable:
▪ Make sure the heating element of the drain tube heater is completely inside
the drain tube.
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block and the earth screw.
▪ Fix the cable with cable ties.
Wires: (2+GND)×0.75mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115W (0.5A)
—