10 | Configuration
Installer reference guide
185
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
# Code Description
[5.3] [6-0B] Eco setpoint:
▪ 30°C~min(50,[6‑0E])°C
Reheat setpoint
Desired reheat tank temperature, used:
▪ in Schedule + reheat mode, during reheat mode: the guaranteed minimum
tank temperature is set by the Reheat setpoint minus the reheat hysteresis.
If the tank temperature drops below this value, the tank is heated up.
▪ during storage comfort, to prioritize the domestic hot water preparation. When
the tank temperature rises above this value, domestic hot water preparation and
space heating/cooling are executed sequentially.
# Code Description
[5.4] [6-0C] Reheat setpoint:
▪ 30°C~min(50,[6‑0E])°C
Schedule
You can set the tank temperature schedule using the schedule screen. For more
information about this screen, see "10.3.7Schedule screen: Example"[4145].
Heat up mode
The domestic hot water can be prepared in 3 different ways. They differ from each
other by the way the desired tank temperature is set and how the unit acts upon it.
# Code Description
[5.6] [6-0D] Heat up mode:
▪ 0: Reheat only: Only reheat operation is
allowed.
▪ 1: Schedule + reheat: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪ 2: Schedule only: The domestic hot water
tank can ONLY be heated according to a
schedule.
See the operation manual for more details.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.