10 | Configuration
Installer reference guide
208
EPRA14~18DAV3+W1 + ETVH16SU18+23EA6V
Daikin Altherma 3 H HT F
4P644738-1 – 2021.02
# Code Description
[9.9.4] [5-05] Limit 1: 0A~50A
[9.9.5] [5-06] Limit 2: 0A~50A
[9.9.6] [5-07] Limit 3: 0A~50A
[9.9.7] [5-08] Limit 4: 0A~50A
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
# Code Description
[9.9.8] [5-09] Limit: Only applicable in case of full time
power limitation mode.
0kW~20kW
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
# Code Description
[9.9.9] [5-09] Limit 1: 0kW~20kW
[9.9.A] [5-0A] Limit 2: 0kW~20kW
[9.9.B] [5-0B] Limit 3: 0kW~20kW
[9.9.C] [5-0C] Limit 4: 0kW~20kW
Priority heater
# Code Description
[9.9.D] [4-01] Power consumption control DISABLED
[4‑08]=0
▪ 0 None : Backup heater and booster heater
can operate simultaneously.
▪ 1 Booster heater: The booster heater is
prioritised.
▪ 2 Backup heater: The backup heater is
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
▪ 0 None : Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
▪ 1 Booster heater: Depending on the
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
▪ 2 Backup heater: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
Note: In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.