Operation manual BRC1E52A7
35
4PW71265-1 – 10.2011
Changing ventilation mode
1
Return Setting
Ventilation
Ventilation rate
Ventilation mode
2/2
• Display the ventilation settings screen.
(See page 34.)
• Press buttons to select
on
the ventilation settings screen.
Press Menu/Enter button to display the ventilation
mode settings screen.
2
Return Setting
Ventilation
Ventilation mode
2/2
Bypass
• Pressing buttons changes the settings in
order as shown below.
Bypass Energy Reclaim Vent Automatic
* Only modes that can be set are displayed.
3
Cool
Set to
Cool
28°C
• Select the desired ventilation mode. Pressing
Menu/Enter button conrms the settings and takes
you back to the basic screen.
(Pressing the Cancel button takes you back to the
previous screen without changing the ventilation
mode.)
Ventilation Mode
Auto mode
Using information from the air conditioner (cooling, heating, fan,
and set temperature) and the total heat exchanger unit (indoor and
outdoor temperatures), mode is automatically changed between
Heat exchanger and Bypass.
Energy reclaim
ventilation mode
Outside air undergoes Heat exchange and is supplied to inside the room.
Bypass mode
Outside air is supplied to inside the room without undergoing heat exchange.
Operation Method
Menu Manipulation