1. The maximum eleva�on (ver�cal) difference between the outdoor unit and the indoor unit is 90 feet.
2. Suc�on line must be installed in a manner to prevent liquid migra�on to the outdoor unit from the
indoor unit.
The condenser unit is shipped with a predetermined factory charge level as shown in the unit serial plate. For longer line sets greater
than 15 feet, add 0.6 ounces of refrigerant per foot.
NOTICE
T
OTAL
R
EFRIGERANT
=
F
ACTORY
C
HARGE
+ (0.6
OZ
./
FT
. * A
DDITIONAL
F
EET
OF
A
CTUAL
L
INE
S
ET
).
BURYING REFRIGERANT LINES
If burying refrigerant lines can not be avoided, use the following checklist.
1. Insulate liquid and suc�on lines separately.
2. Enclose all underground por�ons of the refrigerant lines in waterproof material (conduit or pipe) sealing the ends where
tubing enters/exists the enclosure.
3. If the lines must pass under or through a concrete slab, ensure lines are adequately protected and sealed.