EasyManua.ls Logo

Daikin Enfinity CCH - Communication Module Integration

Daikin Enfinity CCH
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 1049-9 20 www.DaikinApplied.com
MicroTech III Controller With
lonWorks
®
Communication
Module
This manual covers the installation of a Daikin Horizontal
Ceiling Hung Unit - Model CCH, CCW Water Source
Heat Pump. For installation and operation information on
LonWorks Communication Module and other ancillary
control components, see:
IM 927 - MicroTech III Water Source Heat Pump
LonWorks Communication Module
IM 933 - LonMaker Integration Plug-in Tool: For use
with the MicroTech III Unit Controller
IM 955 - MicroTech III Wall Sensor for use with
Microtech III Unit Controller
Figure 16: LonWorks Communication Module
The LonWorks communication module will plug into the
Microtech III unit controller at the CN_LON1 Header (see
on page 22).
Each Daikin water source heat pump can be equipped
with a LonWorks communication module. The
controller is microprocessor-based and is designed
to communicate over a LonWorks communications
network. The unit controller is factory programmed and
tested with all the logic required to monitor and control
the unit. The wall thermostat sets the unit mode of
operation. The unit controller monitors water and air
temperatures, and can communicate fault conditions to a
LonWorks communications network.
The MicroTech III unit controller with communication
module includes a unit-mounted return air, discharge air
and leaving water temperature sensor. Wall mounted
temperature sensors include setpoint adjustment and
tenant override. The user has the capability of substituting
the wall sensor with a duct-mounted return air sensor.
Each unit controller orchestrates the following unit
operations:
Enable heating and cooling to maintain setpoint
based on a room sensor.
Enable fan and compressor operation.
Monitor all equipment protection controls.
Monitor discharge air temperature.
Monitor leaving water temperature.
Relay status of all vital unit functions.
Support optional control outputs.
MicroTech III heat pumps with a MicroTech III unit
controller are LonMarkcertiedanddesignedtobe
linked with a centralized building automation system
through a LonWorks communications network for
centralized scheduling and management of multiple
heat pumps. Wall-mounted room sensors are available
to control the heating and cooling operation of each
MicroTech III Water Source Heat Pump Unit Controller.
Available room sensors include: room sensor with LED
status and tenant override button, room sensor with LED
status, timed-override button, room sensor with LED
status, timed-override button, and setpoint adjustment,
and room sensor with LED status, timed-override button,
setpoint adjustment.
The MicroTech III water source heat pump unit controller
provides control of Daikin water source heat pumps.
The controller enables the mode of operation, monitors
the water and air temperatures, and indicates fault
conditions. Each unit controller is factory programmed,
wired, and tested for effective operation of your Daikin
water source heat pump.
The MicroTech III water source heat pump controller
uses LonWorks technology.
LonMark®3.4certiedapplicationcodeisthecurrent
standard application code for MicroTech III units.
Controls

Related product manuals