Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2] Space heating/cooling=0 (Off) and [C.3] Tank=0 (Off). See
"10.6.12Operation"[4229].
# Code Description
[9.P.5] [7-0C] Mixing valve turning time: Time in
seconds for the mixing valve to turn from one
side to the other.
▪ 20~300sec (default: 125)
10.6.10 Commissioning
Overview
The following items are listed in the submenu:
Commissioning
User profile
Installer settings
Information
Operation
[A] Commissioning
[A.1] Operation test run
[A.2] Actuator test run
[A.3] Air purge
[A.4] UFH screed dryout
About commissioning
See: "11Commissioning"[4236]
10.6.11 User profile
[B] User profile: See "To change the user permission level"[4141].
User profile
Operation
Commissioning
Installer settings
Malfunctioning
10.6.12 Operation
Overview
The following items are listed in the submenu:
Operation
Malfunctioning
User profile
Commissioning
Room
[C] Operation
[C.2] Space heating/cooling
[C.3] Tank
To enable or disable functionalities
In the operation menu, you can separately enable or disable functionalities of the
unit.