Troubleshooting ESIE05-04
3–30 Part 3 Troubleshooting
3
1
3
4
5
1.10 Overview of the Indoor Safety Devices
Thermal protector Thermal fuse fan motor
Abnormal Reset (automatic)
FCQ35, 50, 60, 71B >130°C +/-5°C <83°C +/-20°C N.A.
FCQ100, 125B >140°C +/-5°C <45°C +/-15°C N.A.
FCQ71, 100, 125, 140D N.A. N.A. N.A.
FFQ25, 35, 50, 60B >130°C +/-5°C <83°C +/-20°C N.A.
FBQ35, 50, 60, 71,100, 125B N.A. N.A. >152 +/-2°C
FDQ125, 200, 250B N.A. N.A. >160 °C
FHQ35, 50, 60, 71, 100, 125B >130°C +/-5°C <83°C +/-20°C N.A.
FUQ71, 100, 125B >130°C +/-5°C <83°C +/-20°C N.A.
FAQ71, 100B >130°C +/-5°C <83°C +/-20°C N.A.
FDEQ71, 100, 125B N.A. N.A. >152 +/-2°C