EasyManua.ls Logo

Daikin FCQ60B7V1 - Malfunction of Transmission between MAIN Remote Controller; And SUB Remote Controller

Daikin FCQ60B7V1
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE05-04 Error Codes: System Malfunctions
Part 3 Troubleshooting 3–49
33
4
5
1
3.4 Malfunction of Transmission between MAIN Remote Controller
and SUB Remote Controller (
U8
)
Error code U8
Error generation The error is generated when, in case of controlling with two remote controllers, the microprocessor
detects that the transmission between the indoor unit and the remote controllers (MAIN and SUB) is
not normal over a certain amount of time.
Causes The possible causes are:
Q Transmission error between MAIN remote controller and SUB remote controller
Q Connection among SUB remote controllers
Q Malfunctioning remote controller PCB.
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
TurntheSS-1switchofone
remotecontrollertoMAIN.
TurnOFFthepowersupply,
andrestartoperation.
TurnOFFthepoweronceand
restartoperation.
ReplaceremotecontrollerPCB
ifanyerrorisgenerated.
TurntheSS-1switchofone
remotecontrollertoMAIN.
TurnOFFthepowersupply,
andrestartoperation.
NO
NO
YES YES
YES
NO
Controllingwith
2-remotecontroller
BothSS-1
switchesonremote
controllersareturned
toSUB
SS-1switch
onremotecontroller
PCBisturned
toMAIN

Table of Contents