ESIE05-04 Disassembly and Maintenance
Part 5 Disassembly and Maintenance 5–65
3
5
1
5
5 Take out the two tie
wraps fixing the anti
sweat tube of header and
thermistor.
(Be sure not to take out
other tie wrap.)
Q Heat resistance tie wrap is
used. Be sure to use a heat
resistance tie wrap when
installing new thermistor.
Heat resistance tie wrap
Parts No. :1278921
(Drg No. :4SA90202-1)
6 Pull out the thermistor
from the insertion pipe.
Thermistor for heating :
The upper one wrapped
with a yellow tape
Thermistor for liquid
pipe :
The lower one without
taping
Q Replace thermistor as an
ass'y. (Two thermistors are
bound with special heat
resistance tube.)
Step Procedure Points