EasyManua.ls Logo

Daikin FTK24NMVJU - 4.15 Discharge Pipe Temperature Control

Daikin FTK24NMVJU
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiUS041501E Troubleshooting
Service Diagnosis 68
4.7 Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
Error Code
U4
Method of Error
Detection
The data received from the outdoor unit in signal transmission is checked whether it is normal.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Power supply voltage is not as specified.
Reduction of power supply voltage
Wiring error
Breaking of the connecting wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Short circuit inside the fan motor winding
Defective indoor unit PCB
Disturbed power supply waveform

Table of Contents

Other manuals for Daikin FTK24NMVJU

Related product manuals