Si04-402A Troubleshooting
Service Diagnosis 99
4.22 Output Over Current Detection
Remote
Controller
Display
L5
Method of
Malfunction
Detection
An output over-current is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output over-current input is fed from the output over-current detection circuit to the
microcomputer.
The system will be shut down if the error occurs 255 times.
Clearing condition: Continuous run for about 10 minutes (normal)
Supposed
Causes
Over-current due to defective power transistor
Over-current due to wrong internal wiring
Over-current due to abnormal supply voltage
Over-current due to defective PCB
Error detection due to defective PCB
Over-current due to closed stop valve
Over-current due to compressor failure
Over-current due to poor installation condition

Table of Contents

Other manuals for Daikin FTXG25CVMAW

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTXG25CVMAW and is the answer not in the manual?

Daikin FTXG25CVMAW Specifications

General IconGeneral
BrandDaikin
ModelFTXG25CVMAW
CategoryAir Conditioner
LanguageEnglish

Related product manuals