5 English
Installation Guidelines
•
Whereawallorotherobstacleisinthepathoftheoutdoorunit’sintakeorexhaustairow,followtheinstallationguidelinesbelow.
• Foranyofthebelowinstallationpatterns,thewallheightontheoutletsideshouldbe47-1/4inch(1200mm)orless.
More than
1-15/16 (50)
More than
1-15/16 (50)
More than
5-7/8 (150)
More than
3-15/16 (100)
More than
1-15/16 (50)
More than
3-15/16 (100)
Side view
47-1/4
(1200)
or less
Wall facing one side
Walls facing two sides
Top view
Top view
More than 5-7/8 (150)
More than
11-13/16 (300)
More than
1-15/16 (50)
Walls facing three sides
unit: inch (mm)
unit: inch (mm)
Top view
More than 3-15/16 (100)
More than
13-3/4 (350)
More than
1-15/16 (50)
Walls facing three sides
More than
3-15/16 (100)
More than
13-3/4 (350)
Side view
47-1/4
(1200)
or less
Wall facing one side
More than
1-15/16 (50)
More than
1-15/16 (50)
Top view
More than
3-15/16 (100)
Walls facing two sides
More than
13-3/4 (350)
09/12 class
18/24 class
Outdoor Unit Installation
1. Installing the outdoor unit
1)
When installing the outdoor unit, refer to “Precautions for Selecting the Location and the Outdoor Unit Installation Drawings”.
2) If drain work is necessary, follow the procedures below.