EasyManua.ls Logo

Daikin FTXTA30AW - Page 104

Daikin FTXTA30AW
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ESIE17-19C | Part 5. Appendix 5.1. Field setting
Optimized Heating 4
Page 104 19/08/19 | Version 1.1
8. Press .
9. Select the value to set the desired target temperature:
- 0= -2,0°C
- 1= -1,0°C
- 2= 0°C (factory setting)
- 3= +1,0°C
- 4= +2,0°C
10. Press to confirm.
5.1.1.2.3 To control the indoor unit fan during thermostat off in cooling
1. Press , and simultaneously.
2. Press .
3. Select SU.
4. Press to confirm.
5. Press .
6. Select 4.
7. Press to confirm.
8. Press .
9. Select 0 (0: fan ON, 1: fan OFF).
10. Press to confirm.
5.1.1.2.4 To change auto restart ON to OFF
1. Press , and simultaneously.
2. Press .
3. Select SU.
4. Press to confirm.
5. Press .
6. Select 10.
7. Press to confirm.
8. Press .
9. Select 0 (0: auto restart OFF, 1: auto restart ON).
10. Press to confirm.
5.1.1.2.5 To control cooling mode only
Prerequisite: Stop operation of the unit (via the user interface, operation switch, ...).
Prerequisite: Turn OFF the respective circuit breaker.
1. Cut the jumper J8 on the user interface of the indoor unit.
2. Turn ON the unit using the respective circuit breaker.
3. Start the unit operation (via the user interface, operation switch, ...).
INFORMATION
After power failure, the unit will automatically restart (default setting). It is possible to switch OFF auto restart. For example: after a long power failure, generators have to start-up. As
there is limited energy and the air conditioners do NOT have priority, it is recommended to switch OFF auto restart.

Table of Contents