6 Capacity tables
6 - 1 Cooling Capacity Tables
2
6
FWF-BF
3TW33082-2
NOTES
1. The capacity is only guaranteed at the nominal conditions
Air temperature (°CDB -°CWB) 22-16
Water temperature (Entering °C - Leaving °C) 6-11 7-12 8-13 9-14
Model Air flow
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
FWF02BF
HH 1.4 1.1 4.1 3 1.1 1.0 3.5 2 1.0 0.9 3.1 2 0.8 0.8 2.6 2
H1.2 0.9 3.7 2 1.0 0.8 3.0 2 0.9 0.8 2.6 2 0.7 0.7 2.22
L 1.0 0.8 3.0 2 0.8 0.7 2.5 2 0.7 0.7 2.3 2 0.6 0.6 1.8 2
FWF03BF
HH 1.9 1.2 5.7 10 1.6 1.1 5.6 8 1.4 1.0 4.1 6 1.1 1.0 4.3 5
H 1.6 0.9 4.8 8 1.4 0.8 5.1 7 1.2 0.8 3.4 5 1.0 0.7 3.1 4
L1.2 0.7 3.8 7 1.0 0.6 4.6 6 1.1 0.6 2.8 4 0.7 0.6 2.5 4
FWF04BF
HH 2.4 1.7 7.1 17 2.0 1.5 7.4 13 1.8 1.4 5.3 9 1.5 1.4 5.3 7
H1.9 1.2 5.7 12 1.7 1.1 5.8 8 1.4 1.0 4.2 71.2 1.0 4.4 5
L 1.3 0.7 3.8 7 1.1 0.6 4.6 6 1.1 0.6 2.8 4 0.7 0.6 2.5 4
FWF05BF
HH 3.22.4 9.4 192.5
2.0 7.4 13 2.2 1.9 6.4 10 1.9 1.8 5.8 8
H 2.4 1.6 7.2 122.0 1.5 6.0 9 1.8 1.4 5.2 7 1.5 1.4 4.5 6
L 1.8 1.1 5.4 8 1.5 1.0 4.6 6 1.3 0.9 4.1 6 1.1 0.9 3.5 4
Air temperature (°CDB -°CWB) 25-18
Water temperature (Entering °C - Leaving °C) 6-11 7-12 8-13 9-14
Model Air flow
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
FWF02BF
HH 1.8 1.3 5.7 6 1.5 1.2 4.8 4 1.3 1.1 4.2 4 1.3 1.0 4.1 3
H 1.6 1.2 4.7 4 1.4 1.1 4.1 3 1.3 1.0 3.9 3 1.1 0.9 3.9 3
L 1.3 1.0 4.1 3 1.2 1.0 4.0 3 1.1 0.9 4.130.9 0.8 3.9 3
FWF03BF
HH 2.5 1.5 7.4 13 2.3 1.5 6.9 11 2.1 1.3 6.1 9 1.7 1.2 5.1 7
H 2.2 1.2 6.4 10 2.0 1.1 5.8 8 1.8 1.0 5.2 7 1.5 0.9 4.3 5
L 1.7 0.9 5.0 7 1.5 0.8 4.6 6 1.3 0.8 4.1 5 1.2 0.7 4.1 5
FWF04BF
HH 3.3 2.29.6 20 3.0 2.1 8.8 17 2.6 1.9 7.8 14 2.2 1.7 6.4 10
H 2.6 1.5 7.6 13 2.4 1.4 7.0 122.1 1.3 6.291.8 1.2 5.2 7
L 1.7 0.9 5.0 7 1.5 0.8 4.6 6 1.3 0.8 4.1 5 1.2 0.7 4.1 5
F
WF05BF
HH 4.3 3.1 12.6 32 3.8 2.9 11.226 3.5 2.6 10.1 22 2.8 2.2 8.1 15
H 3.3 2.1 9.6 20 3.0 2.0 8.8 17 2.7 1.8 7.8 14 2.2 1.6 6.3 10
L 2.5 1.4 7.2 122.2 1.3 6.6 10 2.0 1.2 5.8 8 1.7 1.1 5.0 7
FWF-BF
3TW33082-2
NOTES
1. The capacity is only guaranteed at the nominal conditions
Air temperature (°CDB -°CWB) 27-19
Water temperature (Entering °C - Leaving °C) 6-11 7-12 8-13 9-14
Model Air flow
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
FWF02BF
HH 2.2 1.5 6.4 7 2.0 1.5 5.7 6 1.7 1.4 5.3 5 1.6 1.2 4.7 4
H1.9 1.3 5.4 5 1.7 1.3 4.9 4 1.5 1.2 4.4 4 1.4 1.1 4.1 3
L 1.5 1.1 4.4 4 1.4 1.1 4.1 3 1.2 1.0 3.7 3 1.2 0.9 3.4 3
FWF03BF
HH 2.9 1.8 8.5 16 2.7 1.7 7.7 13 2.4 1.6 7.2 122.2 1.4 6.4 10
H 2.5 1.3 7.2 122.3 1.3 6.6 10 2.1 1.2 6.1 9 1.8 1.1 5.3 7
L 2.0 1.0 5.7 8 1.8 1.0 5.2 7 1.6 0.9 4.8 6 1.4 0.8 4.1 5
FWF04BF
HH 3.8 2.5 11.1 25 3.5 2.4 10.0 213.22.29.3 192.8 2.0 8.1 15
H 3.0 1.7 8.7 17 2.8 1.7 8.1 15 2.5 1.6 7.3 122.2 1.4 6.5 10
L 2.0 1.0 5.7 8 1.8 1.0 5.2 7 1.6 0.9
4.8 6 1.4 0.8 4.1 5
FWF05BF
HH 4.9 3.4 14.2 40 4.5 3.3 12.8 33 4.0 3.1 11.8 28 3.6 2.8 10.5 23
H 3.8 2.4 10.925 3.5 2.3 10 21 3.1 2.1 9.2 18 2.8 1.9 8.1 15
L 2.8 1.5 8.2 15 2.6 1.5 7.5 13 2.3 1.4 6.8 11 2.1 1.3 6.29
Air temperature (°CDB -°CWB) 30-22
Water temperature (Entering °C - Leaving °C) 6-11 7-12 8-13 9-14
Model Air flow
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
Total cooling
capacity (kW)
Sensible cooling
capacity (kW)
Water flow
(l/min)
Water pressure
drop (kPa)
FWF02BF
HH 3.0 1.8 9.0 122.8 1.7 8.5 11 2.6 1.6 7.8 92.3 1.5 7.1 8
H 2.6 1.6 7.8 92.5 1.5 7.2 8 2.3 1.4 6.7 7 2.1 1.3 6.0 6
L 2.1 1.3 6.3 7 2.0 1.3 5.8 6 1.8 1.2 5.4 5 1.7 1.1 5.0 5
FWF03BF
HH 4.1 2.1 12.0 29 3.8 2.0 11.226 3.6 1.9 10.5 23 3.3 1.8 9.7 20
H 3.5 1.6 10.1 22 3.2 1.5 9.4 19 3.0 1.4 8.8 17 2.8 1.3 8.2 15
L 2.7 1.2 7.8 14 2.5 1.1 7.4 13 2.4 1.1 6.9 11 2.2 1.0 6.4 10
FWF04BF
HH 5.4 2.9 15.5 46 5.0 2.8 14.6 42 4.7 2.7 13.6 37 4.3 2.5 12.6 32
H4.22.0 12.2 30 4.0 2.0 11.5 27 3.7 1.9 10.7 24 3.4 1.8 10.0 21
L 2.7 1.2 7.8 14 2.5 1.1 7.4 13 2.4 1.1 6.9 11 2.2 1.0 6.4 10
FWF05BF
HH 6.9 4.0 20.0 74 6.5 3.9 19.0 68 6.1 3.7 17.6 59 5.6 3.5 16.3 51
H 5.4 2.8 15.6 47 5.0 2.7 14.6 42 4.7 2.5 13.6 37 4.3 2.4 12.6 32
L3.9 1.8 11.226 3.6 1.7 10.5 23 3.4 1.6 9.9213.2 1.5 9.3 19
ECDEN11-400_FWF-BT-BF.pdf 28 1/03/2011 16:20:03