53
IOM 1264-4
WWW.DAIKINAPPLIED.COM
MAINTENANCE
It is required that the ow switch be mounted such that the
electrical connection and indentation ‘mark’ are pointed in the
direction of ow as shown in Figure 33.
If the ow sensor is to be mounted away from the unit, the sensor
should be mounted on the wall of the outlet pipe of evaporator
and condenser, or in a run of straight pipe that allows 5 to 10
pipe diameters prior to the sensor and 3 to 5 pipe diameters
of straight pipe after the sensor. Flow switch is placed in outlet
pipe to reect ow leaving the barrel. If installation on the
inlet pipe is necessary, contact Chiller Technical Response at
TechResponse@DaikinApplied.com to review the jobsite details.
Figure 33: Mount in Direction of Flow
It is important that the ow switch be mounted so that the probe
is suciently inserted into the uid stream. Figure 34 illustrates
the recommended orientation of the sensor. It may not be
mounted directly on top or directly on the bottom of a horizontal
pipe.
NOTICE
DO NOT alter or relocate factory installed ow switch. If issues exist, contact
Chiller Technical Response at TechResponse@DaikinApplied.com.
Figure 34: Remote Mounting Guidelines for Flow Switch
If needed, the adapter is threaded into the pipe using pipe
sealant appropriate for the application. The ow sensor is
mounted onto the adapter using silicone grease. Carefully apply
lubricant to the inside threads and O-ring so temperature probe
does not become coated with lubricant. Torque the adapter/
sensor connection to 18.5 ft/lbs.
Wiring
Refer to wiring diagram in the unit control panel.
Either AC or DC is used to power the ow switch. The unit
controller’s digital input is a DC signal which is supplied through
the switch output of the ow switch for ow indication. It is
required that the AC and DC commons of power be separated.
Contact Chiller Technical Response for alternate wiring
scenarios.
Flow Switch Setup
The ow switch comes from the factory set at a default velocity
of 20 cm/s. This value is typically well below the minimum water
ow specied for the unit evaporator and condenser so eld
adjustment is required for adequate low ow protection. Table 31
shows the calculated gallons per minute (gpm) for Schedule 40
steel pipe for various uid velocities from 20 cm/s to 300 cm/s.
The ow switch has an overall range of adjustment from 3 cm/s
to 300 cm/s.
Step 1: Adjust ow through the evaporator to the minimum
desired operating gpm. Maintain this ow throughout the setup
procedure.
Step 2: Once steady state minimum desired operating ow is
obtained, perform the ‘Teach’ function on the ow switch. The
‘Teach’ function is initiated by holding down the minus ‘-’ button
on the face of the ow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the ‘Teach’
function is completed, the outer LEDs will ash green as shown
in Figure 35.
Figure 35: Automatic Teach of Setpoint