EasyManua.ls Logo

Daikin Navigator WWV - Flow Switch Wiring and Setup; Flow Switch Setup Procedure; Remote Flow Switch Mounting

Daikin Navigator WWV
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53
IOM 1264-4
WWW.DAIKINAPPLIED.COM
MAINTENANCE
It is required that the ow switch be mounted such that the
electrical connection and indentation ‘mark’ are pointed in the
direction of ow as shown in Figure 33.
If the ow sensor is to be mounted away from the unit, the sensor
should be mounted on the wall of the outlet pipe of evaporator
and condenser, or in a run of straight pipe that allows 5 to 10
pipe diameters prior to the sensor and 3 to 5 pipe diameters
of straight pipe after the sensor. Flow switch is placed in outlet
pipe to reect ow leaving the barrel. If installation on the
inlet pipe is necessary, contact Chiller Technical Response at
TechResponse@DaikinApplied.com to review the jobsite details.
Figure 33: Mount in Direction of Flow
It is important that the ow switch be mounted so that the probe
is su󰀩ciently inserted into the uid stream. Figure 34 illustrates
the recommended orientation of the sensor. It may not be
mounted directly on top or directly on the bottom of a horizontal
pipe.
NOTICE
DO NOT alter or relocate factory installed ow switch. If issues exist, contact
Chiller Technical Response at TechResponse@DaikinApplied.com.
Figure 34: Remote Mounting Guidelines for Flow Switch
If needed, the adapter is threaded into the pipe using pipe
sealant appropriate for the application. The ow sensor is
mounted onto the adapter using silicone grease. Carefully apply
lubricant to the inside threads and O-ring so temperature probe
does not become coated with lubricant. Torque the adapter/
sensor connection to 18.5 ft/lbs.
Wiring
Refer to wiring diagram in the unit control panel.
Either AC or DC is used to power the ow switch. The unit
controller’s digital input is a DC signal which is supplied through
the switch output of the ow switch for ow indication. It is
required that the AC and DC commons of power be separated.
Contact Chiller Technical Response for alternate wiring
scenarios.
Flow Switch Setup
The ow switch comes from the factory set at a default velocity
of 20 cm/s. This value is typically well below the minimum water
ow specied for the unit evaporator and condenser so eld
adjustment is required for adequate low ow protection. Table 31
shows the calculated gallons per minute (gpm) for Schedule 40
steel pipe for various uid velocities from 20 cm/s to 300 cm/s.
The ow switch has an overall range of adjustment from 3 cm/s
to 300 cm/s.
Step 1: Adjust ow through the evaporator to the minimum
desired operating gpm. Maintain this ow throughout the setup
procedure.
Step 2: Once steady state minimum desired operating ow is
obtained, perform the ‘Teach’ function on the ow switch. The
‘Teach’ function is initiated by holding down the minus ‘-’ button
on the face of the ow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the ‘Teach’
function is completed, the outer LEDs will ash green as shown
in Figure 35.
Figure 35: Automatic Teach of Setpoint

Other manuals for Daikin Navigator WWV

Related product manuals