MAINTENANCE
NAVIGATOR WWV/TWVDAIKIN APPLIED
54
Table 31: Flow Volume Calculation
Pipe Size
(inch)
Inside Pipe
Diameter
(inch)
US GPM at the velocities indicated below
GPM
adjustment
per '+' or '-'
key input
Default
20 cm/sec 30 cm/sec 50 cm/sec 75 cm/sec 100 cm/sec 150 cm/sec 200 cm/sec 250 cm/sec 300cm/sec
2 2.06 6.86 10.3 17.2 25.7 34.3 51.5 68.6 85.8 102.9 1.72
2.5 2.46 9.79 14.7 24.5 36.7 49.0 73.4 97.9 122.4 146.9 2.42
3 3.07 15.1 22.7 37.8 56.7 75.6 113.4 151.2 189.0 226.8 3.78
3.5 3.55 20.2 30.3 50.6 75.8 101.1 151.7 202.2 252.8 303.3 5.06
4 4.03 26.0 39.1 65.1 97.7 130.2 195.3 260.4 325.5 390.5 6.51
5 5.05 40.9 61.4 102.3 153.5 204.6 306.9 409.2 511.5 613.7 10.2
6 6.07 59.1 88.6 147.7 221.6 295.5 443.2 590.9 738.7 886.3 14.8
8 7.98 102.3 153.5 255.8 383.7 511.6 767.5 1023.3 1279.1 1534.7 25.6
10 10.02 161.3 241.9 403.2 604.8 806.5 1209.7 1612.9 2016.2 2419.1 39.0
12 11.94 229.0 343.4 572.4 858.6 1144.7 1717.1 2289.5 2861.9 3433.8 57.2
14 13.13 276.8 415.2 692.0 1037.9 1383.9 2075.9 2767.8 3459.8 4151.3 69.2
16 15.00 361.5 542.2 903.6 1355.5 1807.3 2710.9 3614.6 4518.2 5421.2 90.4
18 16.88 457.5 686.3 1143.8 1715.7 2287.6 3431.4 4575.2 5719.0 6862.1 114.4
20 18.81 572.4 853.0 1421.6 2132.4 2843.2 4264.8 5686.4 7108.0 8528.6 142.2
Step 3: After the ‘Teach’ function is completed and the outer
LEDs have ashed, the ow switch will indicate a new setpoint
based upon the current ow which should still be at the steady
state minimum desired operating ow. Figure 36 shows a typical
display for this condition. All LEDs to the left of the SP LED are
lit green. The SP LED is lit RED (or may toggle amber) which
indicates that the ow switch is OPEN. Typically, an increase in
uid ow between 15% to 30% above the ‘Teach’ function ow
is required for the SP LED to turn AMBER and the ow switch to
CLOSE indicating acceptable ow.
Figure 36: Teach Adjustment Complete
In Step 3, the ‘Teach’ function re-adjusted the ow switch SP
while ow was at the minimum desired operating ow. The chiller
will not operate at this ow because the ow switch is OPEN
after performing the ‘Teach’ function. The benet of the ‘Teach’
function is to quickly set the setpoint within the desired operating
range. Additional ‘manual’ adjustment of setpoint is required in
order to allow for chiller operation at this minimum ow. The ‘+’
and ‘-’ buttons on the face of the ow switch allow for the manual
adjustment of the SP. Pressing the ‘+’ button reduces the ow
setpoint while pressing the ‘-’ button increases the ow setpoint.
Each button press, ‘+’ or ‘-‘, changes the ow setpoint by 2.5
cm/s.
Step 4: Press the ‘+’ button until LED ‘9’ begins to ash, as
shown in Figure 37. Opening of ow switch should now occur at
approximately 80% to 90% of minimum ow.
Figure 37: Upper Range of Minimum Flow