EasyManua.ls Logo

Daikin RCS - Emergency Shutdown; OA Damper Flow Station with CO Reset Setup; CO 2 Sensor Wiring

Daikin RCS
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Emergency Shutdown
The terminals 105 & 106 on TB2 can be used for any eld
supplied component that requires a unit emergency shutdown.
When these terminals are used, the factory installed jumper
must be removed.
NOTE: Emergency shutdown Faults can be set to
automatically clear once the condition that caused
the alarm is corrected. This can be accomplished by
navigating to Commission Unit/Alarm Conguration/
Emerg Stop and changing the default No value to
Yes.
Figure 26: Emergency Shutdown Wiring Diagram
OA Damper Flow Station with CO
2
Reset Setup
At the Microtech controller enter password 6363.
Scroll down to “Unit Conguration” and click on it.
Scroll down to “OA Flow Stn” and select “6” for “FS/Rst”
9 OA Flow Station
0 = NONE
1 = DF_015–030 (800)
2 = DF_036–042 (802)
3 = DF_045–075 (047)
4 = DF_080–135 (077)
5 = Generic Flow Station
6 = DGeneric Flow Station w/ CO
2
7 = Ebtron MB
Scroll up to “Apply Changes” and select “yes” which will
cause the controller to restart.
Enter password 6363 then scroll down to “Commission
unit” and click on it.
Scroll down to “Min OA setup” menu and click on it.
Scroll down to Min OA reset and select “IAQ VDC” or
“IAQ mA” depending on the type of sensor installed.
Scroll up to “Apply Changes” and select “yes” which will
cause the controller to restart.
CO
2
Sensor wiring
AI 3 Outdoor Temperature 10K Thermistor (STD) All
Universal Inputs/Outputs
# DI AI DO AO Point Comments Cong. Code Condition
X 1 X CO
2
/Min OA/OA CFM 0–10VDC or 4–20 mA 8 = 1, 2, 3, 5, 6, 7, 8 or 9
X 2 X Low Pressure 1 and 2
1
1K & 2K Ohm Input 3 = 1 & 4 > 1 & 4 < H
X 2 X Chilled Wtr 2–10 VDC 3 = 2 or 3 = 3
On all style units (MPS/DPS/RTU/SCU) the CO
2
sensor
needs to be wired to terminals X1 and M at the Microtech III
Controller. Terminal M is the common for all analog inputs.
Make sure the eld wiring polarity is correct to read a valid
PPM value. See Table 4 on page 14
NOTE: The CO
2
sensor (and all eld installed devices)
must be powered from the same transformer as the
controller to prevent damage to the controller.
fIeld wIrIng
www.DaikinApplied.com 29 IM 919-3 • MICROTECH III CONTROLLER

Related product manuals