• Outdoor Unit • REYQ-T
2
• VRV Systems • REYQ-T
4
2 Specifications
Standard Accessories : Installation and operation manual;
Standard Accessories : Connection pipes;
Sound pressure level Cooling Nom. dBA 58 61 64 65 66
Operation range Cooling Min.~Max. °CDB -5.0~43.0
Heating Min.~Max. °CWB -20~15.5
Water production Space
cooling
Min.~M
ax.
°CDB 10~43
Space
heating
Min.~M
ax.
°CDB -20~20 / 24 (6)
Domest
ic hot
water
Min.~M
ax.
°CDB -20~43
Refrigerant Type R-410A
Charge kg 9.7 9.8 9.9 11.8
TCO
2
eq 20.2 20.5 20.7 24.6
GWP 2,087.5
Refrigerant oil Type Synthetic (ether) oil
Piping connections Liquid Type Braze connection
OD mm 9.52 12.7 15.9
Gas Type Braze connection
OD mm 19.1 22.2 28.6
Discharge gas Type Braze connection
OD mm 15.9 19.1 22.2 28.6
Heat insulation Liquid, Suction gas and HP/LP gas
Piping length OU - IU Max. m 165 (7)
After
branch
Max. m 90 (7)
Total piping length System Actual m 1,000 (7)
Level difference OU - IU Outdoo
r unit in
highest
position
m90 (7)
Indoor
unit in
highest
position
m90 (7)
IU - IU Max. m 15
Defrost method Reversed cycle
Safety devices Item 01 High pressure switch
02 Fan driver overload protector
03 Inverter overload protector
04 PC board fuse
PED Category Category II
Most critical part Name Liquid receiver
Ps*V Bar*l 564 672 824
2-2 Electrical Specifications REYQ8T REYQ10T REYQ12T REYQ14T REYQ16T REYQ18T REYQ20T
Power supply Name Y1
Phase 3N~
Frequency Hz 50
Voltage V 380-415
Voltage range Min. % -10
Max. % 10
Current Nominal running
current (RLA) - 50Hz
Cooling A 7.7 10.5 13.8 15.6 18.5 22.0 28.5
2-1 Technical Specifications REYQ8T REYQ10T REYQ12T REYQ14T REYQ16T REYQ18T REYQ20T