243P362438-3H English
12. Checking of device and installation conditions
Be sure to check the followings.
For those doing electrical work
1 Make sure there is no faulty transmission wiring or loosening of a
nut.
See 9.4. Transmission wiring connection procedure on page20.
2 Make sure there is no faulty power wiring or loosening of a nut.
See 9.5. Power wiring connection procedure on page21.
3 Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular
value in accordance with relevant local and national regulations.
For those doing pipe work
1 Make sure piping size is correct.
See 7.2. Selection of piping material on page9 and 7.4. Selec-
tion of refrigerant branch kits on page10.
2 Make sure insulation work is done.
See 11. Pipe insulation.
3 Make sure there is no faulty refrigerant piping.
See 8. Precautions on refrigerant piping on page14.
13. Makingeldsettings
To continue the conguration of the VRV IV heat recovery system, it is
required to give some input to the printed circuit board of the unit. This
chapter will describe how manual input is possible by operating the
push buttons/DIP switches on the printed circuit board and reading the
feedback from the 7 segment displays.
For VRV IV heat recovery system it is alternatively possible to make
several commissioning eld settings through a personal computer
interface (for this, option EKPCCAB* is required). The installer can
prepare the conguration (off-site) on PC and afterwards upload the
conguration to the system. How to connect the cable is described in
13.3. Connecting the PC congurator to the outdoor unit on
page26.
The contents of the actual settings is discussed and explained in 15.2.
Monitoring function and eld settings on page33.
13.1. Accessing the push buttons on the printed circuit
board
It is not required to open the complete control box to access the
push buttons on the printed circuit board and read out the 7 segment
display (s).
To access you can remove the front inspection door of the front panel
(see gure). Now you can open the inspection door of the control box
front panel (see gure). You can see 3 push buttons and 3 seven-
segment displays and DIP switches.
2
1
1 Front panel
2 Main printed circuit board with 3 seven-segment display
and 3 push buttons
Operate the switches and push buttons with an insulated stick (such
as a closed ballpoint pen) to avoid touching of live parts.
Location of the segment displays, buttons and DIP switches:
BS1 BS2
DS1 DS2
BS3
X27A
1
2
BS1 for changing setting mode
BS2, BS3 for changing eld setting
DS1, DS2 DIP switches
1
7 segment displays (3×)
2 Push buttons
Segment display indications:
Off
Blinking
On
13.2. Operating the push buttons and DIP switches on
the printed circuit board
13.2.1. Operating the push buttons
By operating the push buttons it is possible to:
Perform special actions (automatic refrigerant charge, test run, etc).
Perform eld settings (demand operation, low noise, etc).
Below procedure explains how to operate the push buttons to reach
the required mode in the menu, select the correct setting and modify
the value of the setting. This procedure can be used any time special
settings and regular eld setting are discussed in this manual (see
15.2. Monitoring function and eld settings on page33).
Setting denition: [A-B]=C; A=mode; B=setting; C=setting value. A, B
and C are numerical values for eld settings. Parameter C has to be
dened. It can be a chosen from a set (0, 1, 2, 3, 4, 5, …) or regarded
as an ON/OFF (1 or 0) depending on the contents. This is informed
when the eld setting is explained (see 15.2. Monitoring function and
eld settings on page33).
INFORMATION
During special operation (e.g., automatic refrigerant charging, test
run, etc.) or when an malfunction happened, information will contain
letters and numerical values.
Functions of the push button switches which are located on the
outdoorprintedcircuitboard(A1P)
Turn on the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit (s) is
established and normal, the segment indication state will be as follows
(default situation when shipped from factory):
01_EN_3P362438-3H.indb 24 1/14/2015 10:20:19 AM