283P362438-3H English
14.3. Method for adding refrigerant
14.3.1. Flow chart
Step 1
Calculate additional refrigerant charge amount: R (lbs. (kg))
B
A
C
Step 2+3
Close valves C and A
Open valve B to the liquid line
Execute pre-charging amount: Q (lbs. (kg))
Disconnect the manifold from the suction gas line and the high/low pressure
gas line
R=Q R<Q R>Q
Step 4a
Close valve B
Charging is nished
Fill in the amount on the additional refrigerant
charge label
Go to test run
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 4b
Close valve B
R>Q
Step 5
Open all outdoor unit stop valves
Step 6
Proceed with automatic or manual charge
A: Automatic charge
B: Manual charge
Step 6a
Push BS2 once: 888
Push BS2 for more than 5 seconds
01 pressure equalisation
Step 6b
Activate eld setting [2-20]=1
Unit will start manual refrigerant charging operation.
Depending on ambient conditions, the unit will decide to perform autocharge
operation in heating or cooling mode.
Open valve A
Charge remaining amount of refrigerant P (lbs. (kg))
R=Q+P
Close valve A
Push BS3 to stop manual charging
Charging is nished
Fill in the amount on the additional refrigerant charge label
Go to test run
Continued on next page >>