343P362438-3H English
[1-41]= shows the current heating comfort setting. See 15.3. Energy
saving and optimum operation on page36 for more de-
tails about this setting.
15.2.2. Mode 2
Mode 2 is used to change the eld settings of the system. Consulting
the current eld setting value and changing the current eld setting
value is possible.
In general, normal operation can be resumed without special interven-
tion after changing eld settings.
Some eld settings are used for special operation (e.g., 1 time opera-
tion, recovery/vacuuming setting, manual adding refrigerant setting,
etc.). In such a case, it is required to abort the special operation before
normal operation can restart. It will be indicated in below explanations.
[2-0]= Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional
Cool/Heat selector (KRC19-26A) is used. Depending on the
outdoor unit setup (single outdoor unit setup or multi outdoor
unit setup), the correct setting should be chosen. More
details on how to use the Cool/Heat selector option can be
found in the manual of the Cool/Heat selector.
Default value=0.
• 0=Each individual outdoor unit can select Cool/Heat
operation (by Cool/Heat selector if installed).
• 1=Master unit decides Cool/Heat operation when outdoor
units are connected in multiple system combination (a)
• 2=Sub unit for Cool/Heat operation when outdoor units
are connected in multiple system combination (a)
Change [2-0]=0, 1 or 2 in function of required functionality.
[2-8]= T
e
target temperature during cooling operation
Default value=0.
Value
[2-8]
T
e
target
0 Auto (default)
2 43°F (6°C)
3 45°F (7°C)
4 46°F (8°C)
5 48°F (9°C)
6 50°F (10°C)
7 52°F (11°C)
Change [2-8]=0, 2-7 in function of required operation
method during cooling.
For more information and advice about the impact of these
settings, see 15.3. Energy saving and optimum operation on
page36.
[2-9]= T
c
target temperature during heating operation
Default value=0.
Value
[2-9]
T
c
target
0 Auto (default)
1 106°F (41°C)
3 109°F (43°C)
6 115°F (46°C)
Change [2-9]=0, 1, 3 or 6 in function of required operation
method during heating.
For more information and advice about the impact of these
settings, see 15.3. Energy saving and optimum operation on
page36.
[2-12]= Enable the low noise function and/or power consumption
limitation via external control adaptor (DTA104A61/62)
If the system needs to be running under low noise opera-
tion or under power consumption limitation conditions when
an external signal is sent to the unit, this setting should be
changed. This setting will only be effective when the optional
external control adaptor (DTA104A61/62) is installed.
Default value=0.
To activate this function change [2-12]=1.
[2-18]= Fan high static pressure setting
In order to increase the static pressure the outdoor unit fan
is delivering, this setting should be activated. For details
about this setting, see technical specications.
Default value=0.
To activate this function change [2-18]=1.
[2-20]= Manual additional refrigerant charge
In order to add the additional refrigerant charge amount in
a manual way (without automatic refrigerant charging func-
tionality), following setting should be applied.
Further instructions regarding the different ways to charge
additional refrigerant into your system can be found in chap-
ter 14.3. Method for adding refrigerant on page28.
Default value=0.
To activate this function change [2-20]=1.
To stop the manual additional refrigerant charge opera-
tion (when the required additional refrigerant amount is
charged), push BS3. If this function was not aborted by
pushing BS3, the unit will stop its operation after 30 minutes.
If 30 minutes was not sufcient to add the needed refriger-
ant amount, the function can be reactivated by changing the
eld setting again.
[2-21]= Refrigerant recovery/vacuuming mode
In order to achieve a free pathway to reclaim refrigerant out
of the system or to remove residual substances or to vacu-
um the system it is necessary to apply a setting which will
open required valves in the refrigerant circuit so the reclaim
of refrigerant or vacuuming process can be done properly.
Default value=0.
To activate function change [2-21]=1.
To stop the refrigerant recovery/vacuuming mode, push
BS3. If BS3 is not pushed, the system will remain in refriger-
ant recovery/vacuuming mode.
[2-22]= Automatic low noise setting and level during night time
By changing this setting, you activate the automatic low
noise operation function of the unit and dene the level of
operation. Depending on the chosen level, the noise level
will be lowered (3: Level 3<2: Level2<1: Level1).
The start and stop moments for this function are dened
under setting [2-26] and [2-27].
Default value=0.
To activate function change [2-22]=1, 2 or 3.
[2-25]= Low noise operation level via the external control adaptor
If the system needs to be running under low noise operation
conditions when an external signal is sent to the unit, this
setting denes the level of low noise that will be applied (3:
Level 3<2: Level 2<1: Level 1).
01_EN_3P362438-3H.indb 34 1/14/2015 10:20:22 AM