SiBE041401E Field Settings
Trial Operation and Field Settings 108
3.3 Standby Electricity Saving
Outline This function turns power supply OFF to the outdoor unit and sets the indoor unit into standby
electricity saving mode, thus reducing the power consumption of the air conditioner.
Detail Following procedure is required for turning ON the function.
1. Check that the main power supply is turned OFF. Turn OFF if it has not been turned OFF.
2. Remove the stop valve cover.
3. Disconnect the selective connector for standby electricity saving.
4. Turn ON the main power supply.
20/25/35 class
50 class
Caution Before connecting or disconnecting the selective connector for standby electricity saving, make
sure that the main power supply is turned OFF.
(R18981)
Function ON
Function OFF
(factory set)
(R18926)
Function ON
Function OFF
(factory set)