EasyManua.ls Logo

Daikin SiBE041010 - Output Overcurrent Detection

Daikin SiBE041010
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiBE041010 Troubleshooting
Service Diagnosis 85
4.22 Output Overcurrent Detection
Remote
Controller
Display
L5
Method of
Malfunction
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Decision
Conditions
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats 8 times, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal supply voltage
Defective outdoor unit PCB
Defective compressor

Table of Contents

Related product manuals