7 | Installation
Installer reference guide
53
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
Size-up liquid pipe size
L1 (m)
L1: 15~20 20~25 25~30 30~35
R: 0.35 0.7 1.05
(a)
1.4
(a)
(a)
Only for RZAG100~140.
To determine the additional refrigerant amount (R in kg) (in case of twin, triple
and double twin)
1 Determine G1 and G2.
G1 (m) Total length of <x> liquid piping
x=Ø9.5mm (standard)
x=Ø12.7mm (size‑up)
G2 (m) Total length of Ø6.4mm liquid piping
2 Determine R1 and R2.
If Then
G1>40m
(a)
Use the table below to determine R1
(length=G1−40m)
(a)
and R2 (length=G2).
G1≤40m
(a)
(and G1+G2>40m)
(a)
R1=0.0kg.
Use the table below to determine R2
(length=G1+G2−40m)
(a)
.
(a)
In case of size‑up: Replace 40m by 15m.
Standard liquid pipe size
Length (m)
0~10 10~15 15~20 20~30 30~40 40~45
R1: 0.35 0.7
(a)
0.55
(b)
0.7
(a)
1.05
(a)
1.4
(a)
1.55
(a)
R2: 0.2 0.4 0.4 0.6 0.8
(a)
1.0
(a)
(a)
Only for RZAG100~140.
(b)
Only for RZAG71.
Size‑up liquid pipe size
Length (m)
0~5 5~10 10~15 15~20 20~30 30~40 40~45
R1: 0.35 0.7 1.05
(a)
1.4
(a)
R2: 0.35 0.7
(a)
1.05
(a)
1.4
(a)
(a)
Only for RZAG100~140.
3 Determine the additional refrigerant amount: R=R1+R2.