7 | Installation
Installer reference guide
54
RZAG71~140N2V1+Y1
Sky Air Alpha-series
4P695307-1 – 2022.05
Examples
Layout Additional refrigerant amount (R)
L2=7 m
(Ø6.4 mm)
L3=5 m
(Ø6.4 mm)
L1=45 m (Ø9.5 mm)
RZAG100
Case: Twin, standard liquid pipe size
1 G1 Total Ø9.5 => G1=45m
G2 Total Ø6.4 => G2=7+5=12m
2 Case: G1>40m
R1 Length=G1−40m=5m
=> R1=0.35kg
R2 Length=G2=12m
=> R2=0.4kg
3 R R=R1+R2=0.35+0.4=0.75kg
L2=20 m
(Ø6.4 mm)
L3=17 m
(Ø6.4 mm)
L4=17 m
(Ø6.4 mm)
L1=15 m (Ø9.5 mm)
RZAG125
Case: Triple, standard liquid pipe size
1 G1 Total Ø9.5 => G1=15m
G2 Total Ø6.4 => G2=20+17+17=54m
2 Case: G1≤40m (and G1+G2>40m)
R1 R1=0.0kg
R2 Length=G1+G2−40m=15+54−40=29m
=> R2=0.6kg
3 R R=R1+R2=0.0+0.6=0.6kg
Charging refrigerant: Setup
See "7.5.3Checking refrigerant piping: Setup"[447].
To charge additional refrigerant
WARNING
Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant piping is
connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the gas stop valve
and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
If pump down is needed in case of dismantling or relocating the system, see
"12.3To pump down"[475] for more details.