SiE12-411 Troubleshooting
Service Diagnosis 187
Troubleshooting
Check No.5
Refer to P.206
Check No.6
Refer to P.207
Check No.11
Refer to P.210
Correct.
Reconnect.
Replace the four-way valve
coil.
Replace the outdoor unit
PC board.
Reconnect in position.
Replace a defective
thermistor.
Refer to the refrigerant line
check procedure.
Replace the four-way valve
(defective or dust-clogged).
(Q0353)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Four-way valve coil
disconnected (loose)?
YES
YES
NO
Functioning
NO
Check No. 11
Check the refrigerant line.
Malfunctioning
Harness out of connector?
NO
YES
Disconnect the
harness from
the connector.
Resistance between
harnesses about
1500 ohms?
Malfunctioning
Functioning
Check No. 5
Check the four-way valve
switching output.
YES
NO
Any thermistor disconnected?
Malfunctioning
Functioning
Check No. 6
Check the thermistors.
Check the continuity of the
four-way valve coil and harness.
Water mixed
Shut-off valve defective