Troubleshooting for RA Indoor Unit SiBE18-821_C
362 Troubleshooting
4.6.3 Hall IC Check
Check No.16 1. Check the connector connection.
2. With the power on, operation off, and the connector connected, check the following.
Output voltage of about 5 V between pins 1 and 3.
Generation of 3 pulses between pins 2 and 3 when the fan motor is operating.
If NG in step 1
Æ
Defective PCB
Æ
Replace the PCB.
If NG in step 2
Æ
Defective Hall IC
Æ
Replace the fan motor.
If OK in both steps 1 and 2
Æ
Replace the PCB.
1
Gray (power supply)
Purple (signals)
Blue (grounding)
2
3
(R1990)