390 Troubleshooting
7.6 Moving Part of Electronic Expansion Valve (Y1E, Y3E)
Abnormality
Remote
Controller
Display
E9
Method of
Malfunction
Detection
System checks if the connector is disconnected, and the detection is based on the continuity of
electronic expansion valve coil.
Malfunction
Decision
Conditions
No current is detected in the common (COM [+]) when power supply is ON.
Supposed
Causes
Disconnection of connectors for electronic expansion valve Y1E or Y3E
Defective moving part of electronic expansion valve
Defective main PCB (A1P)