SiBE18-821_C Outdoor Unit
Removal Procedure 449
8 Disconnect the brazed
part of the solenoid
valve.
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Step
Procedure Points
(R12983)
Solenoid valve for
hot gas bypass
Solenoid valve for unloading
(R12984)