Error Codes and Description SiBE18-821_C
350 Troubleshooting
3. Error Codes and Description
Error code Description Reference page
RA Indoor
Unit
SA Indoor
Unit
BP Unit Outdoor
Unit
Indoor
Unit
A1 Indoor unit PCB abnormality 352 363
A3 Drain level control system abnormality 364
A5 Freeze-up protection control or heating peak-cut
control
353
A6 Fan motor or related abnormality 355, 356 366
A7 Swing motor look 367
A9 Electronic expansion valve abnormality 376
AF Drain system abnormality 368
C4 Thermistor or related abnormality 358 369
C5 Thermistor or related abnormality 370
C7 Front panel open / close fault 359
C9 Thermistor or related abnormality 358 371
CJ Remote controller thermistor abnormality 372
Outdoor
Unit
E1 Outdoor unit PCB abnormality 383
E2 BP unit PCB abnormality 377
E3 Actuation of high pressure switch 384
E4 Actuation of low pressure switch 386
E5 Compressor motor lock 388
E7 Outdoor fan motor abnormality 389
E9 Moving part of electronic expansion valve (Y1E, Y3E)
abnormality
———390
F3 Discharge pipe temperature abnormality 392
F6 Refrigerant overcharged 393
H9 Outdoor temperature thermistor (R1T) abnormality 394
J0 BP liquid or gas pipe thermistor abnormality 378
J3 Discharge pipe thermistor (R2T) abnormality 395
J5 Suction pipe thermistor (R3T, R5T) abnormality 396
J6 Outdoor heat exchanger thermistor (R4T)
abnormality
———397
J7 Outdoor liquid pipe thermistor (R7T) abnormality 398
J9 Subcooling heat exchanger gas pipe thermistor
(R6T) abnormality
———399
JA High pressure sensor abnormality 400
JC Low pressure sensor abnormality 401
L1 Outdoor unit PCB abnormality 402
L4 Radiation fin temperature rise 403
L5 Inverter compressor abnormality 404
L8 Inverter current abnormality 405
L9 Inverter start-up error 406
P1 High voltage of capacitor in main inverter circuit 407
P4 Radiation fin thermistor abnormality 408
System U0 Low pressure drop due to refrigerant shortage or
electronic expansion valve abnormality
———409
U2 Power supply insufficient or instantaneous failure 411
U3 Check operation is not conducted. 412
U4 Transmission error between indoor unit and BP unit 379
U5 Transmission error between remote controller and
indoor unit
373 413
U8 Transmission error between main and sub remote
controllers
374 414
U9 Transmission error between indoor unit and outdoor
unit in the same system
———415