Troubleshooting by Error Code SiUS331604E
159 Service Diagnosis
4.16 Humidity Sensor System Abnormality
Error Code CC
Applicable
Models
FXFQ
Method of Error
Detection
Even if an error occurs, operation still continues.
Error is detected according to the moisture (output voltage) detected by the moisture sensor.
Error Decision
Conditions
When the moisture sensor is disconnected or short circuited
Supposed
Causes
Defective sensor
Disconnection
Troubleshooting
Note: 1. To delete the history, the ON/OFF button of the remote controller must be pressed and held for
5 seconds in the check mode.
2. To display the code, the INSPECTION/TEST Operation button of the remote controller must be
pressed and held in the normal mode.
3. If CC is displayed even after replacing the humidity sensor PCB assy (A2P) and taking the steps
1 and 2, replace the indoor unit PCB assy (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
Is "CC"
displayed on the
remote controller?
(2)
YES
NO
Does it
function normally?
Remove the humidity sensor
from the indoor unit PCB
and insert it again.
It is normal.
(Poor connector contact)
Replace the humidity sensor
PCB assy (A2P).
(3)
It is believed that external factors
(noise or else) other than failure
caused the error.
Delete the error code history
from the remote controller.
(1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ36TAVJU and is the answer not in the manual?

Daikin VRV IV-S RXTQ36TAVJU Specifications

General IconGeneral
BrandDaikin
ModelVRV IV-S RXTQ36TAVJU
CategoryHeat Pump
LanguageEnglish

Related product manuals