SiUS331604E Other Control
Functions and Control 50
5. Other Control
5.1 Demand Operation
In order to reduce power consumption, the outdoor unit capacity is reduced forcibly with control by using Demand
Setting 1.
To enable this operation, the additional setting of Constant Demand Setting is required.
Demand setting 1
Other protection control functions have precedence over the above operation.
5.2 Heating Operation Prohibition
Heating operation is prohibited above 24°CDB (75.2°FDB) outdoor air temperature.
Level Standard for upper limit of power consumption
Level 1 Approx. 60%
Level 2 (Factory setting) Approx. 70%
Level 3 Approx. 80%