Operation manual
19
HXHD125A7V1B
VRVIII system indoor unit
4PW62585-1 – 11.2010
5.13. Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 Installation related setting
(a)
22~31—
01 Installation related setting
(a)
0 –5~5 0.5 °C
02 Not applicable. Do not change the default value. 1 — — —
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1 — —
04 Not applicable. Do not change the default value. 1 — — —
1 Automatic storage timing for domestic water heating
00 Status: night time storage 1 (ON) 0/1 — —
01 Night time storage start time 1:00 0:00~23:00 1:00 hour
02 Status: day time storage 0 (OFF) 0/1 — —
03 Day time storage start time 15:00 0:00~23:00 1:00 hour
2 Automatic setback function
00 Status: setback operation 1 (ON) 0/1 — —
01 Setback operation start time 23:00 0:00~23:00 1:00 hour
02 Setback operation stop time 5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 45 25~80 1 °C
4 Disinfection function
00 Status: disinfection operation 1 (ON) 0/1 — —
01 Disinfection operation day selection Fri Mon~Sun — —
02 Disinfection operation start time 23:00 0:00~23:00 1:00 hour
5 Automatic setback and disinfection set point
00 Set point: disinfection operation temperature 70 60~75 5 °C
01 Disinfection operation time duration 10 5~60 5 min
02 Leaving water setback temperature 50~101°C
03 Room setback temperature 18 17~23 1 °C
04 Not applicable. Do not change the default value. 0 — — —
6 Option setup
00 Installation related setting
(a)
0 (OFF) 0/1 — —
01 Installation related setting
(a)
0 (OFF) 0/1 — —
02 Not applicable. Do not change the default value. 0 — — —
03 Not applicable. Do not change the default value. 0 — — —
04 Installation related setting
(a)
0 0/2 1 —
7 Option setup
00 Not applicable. Do not change the default value. 0 — — —
01 Not applicable. Do not change the default value. 0 — — —
02 Installation related setting
(a)
0 (A) 0/1 — —
03 Installation related setting
(a)
0 (OFF) 0/1 — —
04 Installation related setting
(a)
0 (OFF) 0/1 — —
8 Option setup
00 Installation related setting
(a)
1 (ON) 0/1 — —
01 Not applicable. Do not change the default value. 1 — — —
02 Not applicable. Do not change the default value. 0 — — —
03 Status: low noise level 11~31—
04 Installation related setting
(a)
0 0~2 1 —