24 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
*)EmergencycoolingwilltakeeectwhenthereislackofsignalfromadenedS3orS4sensor.Theregulationwillcontinuewitharegisteredaverage
cutinfrequency.Therearetworegisteredvalues–onefordayoperationandonefornightoperation.
Operating status (Measurement)
Thecontrollergoesthroughsomeregulatingsituationswhereitisjustwaitingfor
thenextpointoftheregulation.Tomakethese“whyisnothinghappening”situations
visible,youcanseeanoperatingstatusonthedisplay.Pushbriey(1s)theupper
button.Ifthereisastatuscode,itwillbeshownonthedisplay.Theindividualstatus
codeshavethefollowingmeanings:
Ctrl. state:
(Showninallmenudisplays)
Normal regulation S0 0
Waitingforendofthecoordinateddefrost S1 1
Whenthecompressorisoperatingitmustrunforatleastxminutes. S2 2
Whenthecompressorisstopped,itmustremainstoppedforatleastxminutes. S3 3
Theevaporatordripsoandwaitsforthetimetorunout S4 4
Refrigeration stopped by main switch. Either with r12oraDI-input S10 10
Refrigeration stopped by thermostat S11 11
Defrost sequence. Defrost in progress S14 14
Defrost sequence.Fandelay—waterattachestotheevaporator S15 15
RefrigerationstoppedduetoopenONinputorstoppedregulation S16 16
Doorisopen.DIinputisopen S17 17
Melt function in progress. Refrigeration is interrupted S18 18
Modulating thermostat control S19 19
Emergency cooling due to sensor error S20 20
Regulationproblemintheinjectionsfunction S21 21
Start-upphase2.Evaporatorbeingcharged S22 22
Adaptivecontrol S23 23
Start-up phase 1. Signal reliability from sensors is controlled S24 24
Manual control of outputs S25 25
No refrigerant selected S26 26
Case cleaning S29 29
Forcedcooling S30 30
Delay on outputs during start-up S32 32
Heatfunctionr36isactive S33 33
Other displays:
The defrost temperature cannot be displayed. There is stop based on time non
Defrostinprogress/Firstcoolingafterdefrost -d-
Passwordrequired.Setpassword PS
Regulationisstoppedviamainswitch OFF