28 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Menu survey
SW=1.5x
Parameter EL-diagram page 12 or 13
Min.-value Max.-value
Factory
setting
Actual
setting
Function Code 1 2 3 4 5 6 7 8 9 10
Normal operation
Temperature(setpoint) - - - 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
Thermostat
Dierential r01 1 1 1 1 1 1 1 1 1 1 0.1 K 20 K 2
Max. limitation of setpoint setting
r02 1 1 1 1 1 1 1 1 1 1 -49°C 50°C 50
Min. limitation of setpoint setting
r03 1 1 1 1 1 1 1 1 1 1 -50°C 49°C -50
Adjustmentoftemperatureindication
r04 1 1 1 1 1 1 1 1 1 1 -10 10 0
Temperatureunit(°C/°F)
r05 1 1 1 1 1 1 1 1 1 1 0/°C 1/F 0/°C
CorrectionofthesignalfromS4
r09 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
CorrectionofthesignalfromS3
r10 1 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
Manualservice,stopregulation,startregulation(-1,0,1)
r12 1 1 1 1 1 1 1 1 1 1 -1 1 0
Displacement of reference during night operation
r13 1 1 1 1 1 1 1 1 1 1 -50 K 50 K 0
Denethermostatfunction
1=ON/OFF,2=Modulating
r14 1 1 1 1 1 1 1 1 1 1 1 2 1
Denitionandweighting,ifapplicable,ofthermostatsen-
sors-S4%(100%=S4,0%=S3)
r15 1 1 1 1 1 1 1 1 0% 100% 100
Time between melt periods
r16 1 1 1 1 1 1 1 1 1 1 0 hrs 10 hrs 1
Duration of melt periods
r17 1 1 1 1 1 1 1 1 1 1 0 min. 30min. 5
Temperature setting for thermostat band 2 .Asdierential
use r01
r21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 2
Correction of the signal from S6 r59 1 1 1 1 1 1 1 1 1 -10 K 10 K 0
Denitionandweighting,ifapplicable,ofthermostatsen-
sors whennightcoverison.(100%=S4,0%=S3)
r61 1 0% 100% 100
Heatfunction
Neutral zone between refrigeration and heat function
r62 1 0 K 50 K 2
Time delay at switch between refrigeration and heat
function
r63 1 0 min. 240min. 0
Alarms
Delay for temperature alarm
A03 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 30
Delay for door alarm
A04 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 60
Delay for temperature alarm after defrost
A12 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 90
Highalarmlimitforthermostat1
A13 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
Lowalarmlimitforthermostat1
A14 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
Highalarmlimitforthermostat2
A20 1 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
Lowalarmlimitforthermostat2
A21 1 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
HighalarmlimitforsensorS6atthermostat1
A22 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
LowalarmlimitforsensorS6atthermostat1
A23 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
HighalarmlimitforsensorS6atthermostat2
A24 1 1 1 1 1 1 1 1 1 -50°C 50°C 8
LowalarmlimitforsensorS6atthermostat2
A25 1 1 1 1 1 1 1 1 1 -50°C 50°C -30
S6alarmtimedelay
Withsetting=240theS6alarmwillbeomitted
A26 1 1 1 1 1 1 1 1 1 0 min. 240min. 240
AlarmtimedelayorsignalontheDI1input
A27 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 30
AlarmtimedelayorsignalontheDI2input
A28 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 30
Signalforalarmthermostat.S4%(100%=S4,0%=S3)
A36 1 1 1 1 1 1 1 1 0% 100% 100
DelayforS6(productsensoralarm)afterdefrost A52 1 1 1 1 1 1 1 1 1 0 min. 240min. 90
Compressor
Min.ON-time c01 1 1 1 1 0 min. 30min. 0
Min.OFF-time c02 1 1 1 1 0 min. 30min. 0
Time delay for cutin of comp.2
c05 1 0 sec 999sec 5
Defrost
Defrost method:0=none,1=EL,2=Gas d01 1 1 1 1 1 1 1 1 1 1 0/No 2/GAs 1/EL
Defrost stop temperature
d02 1 1 1 1 1 1 1 1 1 1 0°C 50°C 6
Intervalbetweendefroststarts
d03 1 1 1 1 1 1 1 1 1 1 0hrs/O 240hrs 8
Max. defrost duration
d04 1 1 1 1 1 1 1 1 1 1 0 min. 360min. 45
Displacement of time on cutin of defrost at start-up
d05 1 1 1 1 1 1 1 1 1 1 0 min. 240min. 0
Dripotime
d06 1 1 1 1 1 1 1 1 1 1 0 min. 60min. 0
Delay for fan start after defrost
d07 1 1 1 1 1 1 1 1 1 1 0 min. 60min. 0
Fanstarttemperature
d08 1 1 1 1 1 1 1 1 1 1 -50 °C 0 °C -5
Fancutinduringdefrost
0: Stopped
1: Running
2: Running during pump down and defrost
d09 1 1 1 1 1 1 1 1 1 1 0 2 1
Defrost sensor:0=Stopontime,1=S5,2=S4,3=Sx
(Application1-8and10:bothS5andS6.
Application9:S5andS5B)
d10 1 1 1 1 1 1 1 1 1 1 0 3 0