AK-CC550 Manual RS8EN502 © Danfoss 02-2010 27
Case Room
Defrost stop on
time
Defrost stop
on S5
Defrost stop on
time
Defrost stop
on S5
Preset settings(o62) 1 2 3 4 5 6
Temperature(SP)
2°C -2°C -28°C 4°C 0°C -22°C
Max.temp.setting(r02)
6°C 4°C -22°C 8°C 5°C -20°C
Min.temp.setting(r03)
0°C -4°C -30°C 0°C -2°C -24°C
Sensorsignalforthermostat.S4%(r15)
100% 0%
Alarmlimithigh(A13)
8°C 6°C -15°C 10°C 8°C -15°C
Alarmlimitlow(A14)
-5°C -5°C -30°C 0°C 0°C -30°C
Sensorsignalforalarmfunct.S4%(A36)
0% 100% 0%
Intervalbetweendefrost(d03)
6h 6h 12h 8h 8h 6h
Defrostsensor:0=time,1=S5,2=S4(d10)
0 1 1 0 1 1
DI1cong.(o02)
Casecleaning(=10) Doorfunction(=2)
SensorsignalfordisplayviewS4%(017)
0%
Note:Forapplications9and10thesensorweightingfortheS3/S4sensorsisnotusedforthethermostat,alarmthermostatanddisplayreadingsasthe
sensorusesarepredened.