EasyManua.ls Logo

Danfoss AK-CC 550 - Operation and Setup Guide; Display, Buttons, and Alarms; Initial Setup Procedure

Danfoss AK-CC 550
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 Manual RS8EN502 © Danfoss 02-2010 AK-CC 550
Light-emitting diodes (LED) on front panel
TheLED’sonthefrontpanelwilllightupwhentherelevantrelay
isactivated.
= Refrigeration
= Defrost
=Fanrunning
The light-emitting diodes will flash when there is an alarm.
Inthissituationyoucandownloadtheerrorcodetothedisplay
andcancel/signforthealarmbygivingthetopbuttonabrief
push.
The buttons
Whenyouwanttochangeasetting,theupperandthelower
buttonswillgiveyouahigherorlowervaluedependingonthe
buttonyouarepushing.Butbeforeyouchangethevalue,you
musthaveaccesstothemenu.Youobtainthisbypushingthe
upper button for a couple of seconds - you will then enter the col-
umnwithparametercodes.Findtheparametercodeyouwantto
changeandpushthemiddlebuttonsuntilvaluefortheparameter
isshown.Whenyouhavechangedthevalue,savethenewvalue
by once more pushing the middle button.
Examples
Set menu
1.Pushtheupperbuttonuntilaparameterr01isshown
2.Pushtheupperorthelowerbuttonandndthatparameteryou
want to change
3.Pushthemiddlebuttonuntiltheparametervalueisshown
4.Pushtheupperorthelowerbuttonandselectthenewvalue
5.Pushthemiddlebuttonagaintofreezethevalue.
Cutout alarm relay / receipt alarm/see alarm code
•Ashortpressoftheupperbutton
Ifthereareseveralalarmcodestheyarefoundinarollingstack.
Pushtheuppermostorlowermostbuttontoscantherolling
stack.
Set temperature
1.Pushthemiddlebuttonuntilthetemperaturevalueisshown
2.Pushtheupperorthelowerbuttonandselectthenewvalue
3.Pushthemiddlebuttonagaintoconcludethesetting.
Reading the temperature at defrost sensor (Or product sensor, if
selected in o92.)
•Ashortpressofthelowerbutton
Manuel start or stop of a defrost
•Pushthelowerbuttonforfourseconds.
Display
Thevalueswillbeshownwiththreedigits,andwithasettingyou
can determine whether the temperature is to be shown in °C or in
°F.
Operation
Get a good start
Withthefollowingprocedureyoucanstartregulationveryquick-
ly:
1Openparameterr12andstoptheregulation(inanewandnot
previouslysetunit,r12willalreadybesetto0whichmeans
stoppedregulation.)
2 Select electrical connection based on the drawings on page 12
and13
3Openparametero61andsettheelectricconnectionnumberin
it
4Nowselectoneofthepresetsettingsfromthetableonpage27.
5Openparametero62andsetthenumberforthearrayofpreset-
tings. The few selected settings will now be transferred to the
menu.
6 Openparametern57andselectmethodformeasuringof
evaporatorpressurePeorS1(factorysettingisPepressure
transmitter)
7 IfpressuretransmitterPeisusedyoumustselectrefrigerantvia
parametero30
8Openparameterr12andstarttheregulation
9Gothroughthesurveyoffactorysettings.Thevaluesinthegrey
cellsarechangedaccordingtoyourchoiceofsettings.Makeany
necessarychangesintherespectiveparameters.
10Fornetwork.Settheaddressino03
11 Send address to system unit:
•MODBUS:Activatescanfunctioninsystemunit
•Ifanotherdatacommunicationcardisusedinthecontroller:
-LONRS485:Activatethefunctiono04

Other manuals for Danfoss AK-CC 550

Related product manuals