AK-CC 550A  Manual RS8FS402 © Danfoss 2016-03  13
5 
6 
 
7 
 
9 
 
10 
 
8 
 
The following uses have some special functions 
which in brief are:
Application 5 
”Two-compressor” operation.
The two compressors must be of the same size. 
On start-up (after defrosting, operational stop, 
etc.) both compressors are started with a set time 
shift. One compressor starts at half the dierential 
so that an optimum adaptation of compressor 
capacity takes place for the current load in the 
appliance/room. There is automatic runtime 
equalisation between the compressors.
For a more detailed description please refer to 
earlier sections in the manual.
Application 6
Hot gas defrosting.
Hot gas defrosting is adapted to commercial 
appliances/rooms with limited system lling. 
One relay controls the main valve in the suction 
line. 
A changeover relay controls both the hot gas 
valve and the drain valve. 
This means that there is no time delay between 
stops of hot gas and start of draining.
Application 7
Control of night blinds
Night blinds follow the status of the light function 
– when the light is switched on, the night blinds 
are up and when the light is switched o, the 
night blinds are down. In addition a digital input 
provides the option of forced opening of the 
blinds so that the appliance can be lled with 
products.
 
Application 8 
Heat thermostat
The heat thermostat is typically used if the 
temperature is to be controlled within narrower 
limits, e.g. for cutting rooms, etc. The heating 
thermostat can be set as a dierence in relation to 
the cutout limit for the refrigeration thermostat so 
that simultaneous refrigeration and heating are 
avoided. 
Application 9 
Two refrigeration sections – two defrost outputs
This application is for refrigeration appliances with 
one valve, two evaporators and two refrigeration 
sections. The temperature is controlled and is 
always alarm monitored according to the S4 
temperature. For this the product sensor is used as 
a defrosting stop sensor for evaporator no. 2.
Application 10 
Two refrigeration sections – individual alarm/
display via S3
This application is for refrigeration appliances with 
one valve, one evaporator and two refrigeration 
sections. The temperature is always controlled 
according to the S4 temperature. The product 
sensor is used as an extra S3 sensor for section 
no. 2. Alarm monitoring and display readings take 
place individually via the "S3" sensors in each 
refrigeration section.