6  Manual RS8FS402 © Danfoss 2016-03  AK-CC 550A
Hot gas application
Defrost
Depending on the application you may choose between the fol-
lowing defrost methods:
Natural:   Here the fans are kept operating during the defrost
Electric:    The heating element is activated
Hotgas:  Here the solenoid valves are controlled so that the   
  hotgas can ow through the evaporator
Defrost sequence
1) Pump down
2) Defrost
3) Waiting position after defrost
4) Draining (drain delay. Hotgas only)
5) Drip o
6) Delay of fan
Hot gas defrost (application 6 only)
This type of connection can be used on systems with hotgas 
defrost, but only in small systems in, say, supermarkets – the 
functional content has not been adapted to systems with large 
charges.
Relay 2 is used for the suction valve
Relay 4’s change-over function is used by the bypass valve and hot 
gas valve, respectively.
If the valves PMLX and GPLX are used, the delay time “d23” will 
have to be properly set.
During hot gas defrosting, it is not possible to start a manual 
defrosting cycle with the “DI” functions or with a touch on the 
controller’s lower button.
Drip tray heating element
It is possible to control a heating element in the drip tray for 
hot gas defrosting. When defrosting is commenced, the heating 
element is activated. The heating element remains activated until 
a set time after defrosting has ended by time or temperature.
Start of defrost
A defrost can be started in dierent ways
Interval: Defrost is started at xed time intervals, say, every  
 eighth hour. An interval must ALWAYS be set to 
a "higher" value than the period set between two 
defrostings when a schedule or network signal is used.
Refrigeration time: Defrost is started at xed refrigeration time 
intervals, in other words, a low need for refrigeration will 
”postpone” the defrost
Schedule: Here defrost can be started at xed times of the  
 day and night. However, max. 6 times
Contact: Defrost is started with a contact signal on a digital input
Network: The signal for defrost is received from a system unit
  via the data communication
Adaptive defrost: Here defrosting is started based on intelligent 
registering of evaporator performance.
Manual: An extra defrost can be activated from the controller’s 
lower-most button (though, not with application 6)  
or via a parameter setting.
All the mentioned methods can be used at random – if just of 
them is activated a defrost will be started.
Stop of defrost
Defrosting can be stopped by either:
• Time
• Temperature (with time as safety). 
Compressor
If the defrosting method is set to “Gas,” the compressor will be “On” 
during the defrost cycle.