Danfoss AK-CC 550A - Auxiliary schedule for settings (quick-setup)

Danfoss AK-CC 550A
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AK-CC 550A Manual RS8FS402 © Danfoss 2016-03 27
Case Room
Defrost stop on
time
Defrost stop
on S5
Defrost stop on
time
Defrost stop
on S5
Preset settings (o62) 1 2 3 4 5 6
Temperature (SP)
2°C -2°C -28°C 4°C 0°C -22°C
Max. temp. setting (r02)
6°C 4°C -22°C 8°C 5°C -20°C
Min. temp. setting (r03)
0°C -4°C -30°C 0°C -2°C -24°C
Sensor signal for thermostat. S4% (r15)
100% 0%
Alarm limit high (A13)
8°C 6°C -15°C 10°C 8°C -15°C
Alarm limit low (A14)
-5°C -5°C -30°C 0°C 0°C -30°C
Sensor signal for alarm funct.S4% (A36)
0% 100% 0%
Interval between defrost (d03)
6 h 6h 12h 8h 8h 6h
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
0 1 1 0 1 1
DI1 cong. (o02)
Appliance cleaning (=10) Door function (=2)
Sensor signal for display view S4% (017)
0%
Note: For applications 9 and 10 the sensor weighting for the S3/S4 sensors is not used for the thermostat, alarm thermostat and display readings as the
sensor uses are predened.
Auxiliary schedule for settings (quick-setup)