EasyManua.ls Logo

Danfoss AK-CC55 - Appliance Shutdown and Defrost; Defrost Methods and Start Options

Danfoss AK-CC55
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single Coil - continued R-W Code 1 2 3 4 5 6 7 8 9 Min. Max. Fac. Actual
Real time clock
Defrost start via defrost schedule: 0/off=no.
1/on=yes
1-2 t00 1 1 1 1 1 1 1 1 1 0/off 1/on 0/off
Six start times for defrost.
Setting of hours.
0=OFF
1-2 t01 -
t06
1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
Six start times for defrost.
Setting of minutes.
0=OFF
1-2 t11 -
t16
1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
Clock - Setting of hours
0-1 t07 1 1 1 1 1 1 1 1 1 0 hrs 23 hrs 0
Clock - Setting of minutes
0-1 t08 1 1 1 1 1 1 1 1 1 0 min. 59 min. 0
Clock - Setting of date
0-1 t45 1 1 1 1 1 1 1 1 1 1 day 31 days 1
Clock - Setting of month
0-1 t46 1 1 1 1 1 1 1 1 1 1 mon. 12 mon. 1
Clock - Setting of year
0-1 t47 1 1 1 1 1 1 1 1 1 0 years 99 years 0
Defrost schedule for Mondays is active at On/1 1-2 t51 1 1 1 1 1 1 1 1 1 0/O 1/On 1/On
Defrost schedule for Tuesdays is active at On/1 1-2 t52 1 1 1 1 1 1 1 1 1 0/Off 1/On 1/On
Defrost schedule for Wednesdays is active at On/1 1-2 t53 1 1 1 1 1 1 1 1 1 0/O 1/On 1/On
Defrost schedule for Thursdays is active at On/1 1-2 t54 1 1 1 1 1 1 1 1 1 0/O 1/On 1/On
Defrost schedule for Fridays is active at On/1 1-2 t55 1 1 1 1 1 1 1 1 1 0/Off 1/On 1/On
Defrost schedule for Saturdays is active at On/1 1-2 t56 1 1 1 1 1 1 1 1 1 0/O 1/On 1/On
Defrost schedule for Sundays is active at On/1 1-2 t57 1 1 1 1 1 1 1 1 1 0/Off 1/On 1/On
Humidity
Setpoint for cut-in of humidity function 0-2 h23 1 0 % 100 % 70
Difference for humidity function 1-2 h24 1 1 % 30 % 5
Alarm limit for high humidity (too damp) 1-2 h25 1 0 % 100 % 100
Alarm limit for low humidity (too dry) 1-2 h26 1 0 % 100 % 0
Delay time for a humidity alarm 1-2 h27 1 0 min. 240 min. 60
Humidity function during defrosting 1-2 h28 1 0/Off 1/On 0/Off
Setpoint for RH% at input signal on 0 V 1-2* h29 1 0 % "h30" 0
Setpoint for RH% at input signal on 10 V 1-2* h30 1 "h29" 100 % 100
Use humidity control 1-2* h31 1 0/Off 1/On 0/Off
Miscellaneous
Delay of output signals after power failure 1-2 o01 1 1 1 1 1 1 1 1 1 0 sec 600 sec 5
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with
alarm when open. 3=door alarm when open. 4=defrost
start (pulse-signal). 5=ext.main switch. 6=night
operation 7=thermostat band changeover (activate
r21). 8=alarm function when closed. 9=alarm function
when open. 10=Appliance cleaning (pulse signal).
11=forced cooling at hot gas defrost, 12=Open night
cover. 14=Refrigeration stopped (forced closing).
15=case shutdown. 16=light. 20=Refrigerant alarm.
21= adaptive liquid control when short-circuited.
1-2* o02 1 1 1 1 1 1 1 1 1 0 21 0
Network address 1-3* o03 1 1 1 1 1 1 1 1 1 0 240 0
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at Lon 485)
1-2 o04 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/Off
Access code 3 (all settings) 3-3 o05 1 1 1 1 1 1 1 1 1 0 999 0
Used sensor type: 0=Pt1000, 1=PTC1000, 2=Ntc5K,
3=Ntc10K. (S2 and S6 are not affected. They are always
Pt1000 ohms)
1-3* o06 1 1 1 1 1 1 1 1 1 0/Pt 3/N10 0/Pt
Max. hold time after coordinated defrost 1-2 o16 1 1 1 1 1 1 1 1 1 0 min. 360 min. 20
Select signal for display view. S4%
(100%=S4, 0%=S3)
1-2 o17 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Pressure transmitter working range – min. value 1-3* o20 1 1 1 1 1 1 1 1 1 -1 bar 5 bar -1
Pressure transmitter working range – max. value 1-3* o21 1 1 1 1 1 1 1 1 1 6 bar 200 bar 12
© Danfoss | DCS (vt) | 2019.07
12 | AN294432763974en-000201

Other manuals for Danfoss AK-CC55

Related product manuals