EasyManua.ls Logo

Danfoss AK-CC55 - Defrost Operation Details; Defrost Start, Stop, and Fan;Compressor Operation; Coordinated Defrost

Danfoss AK-CC55
18 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single Coil - continued R-W Code 1 2 3 4 5 6 7 8 9 Min. Max. Fac. Actual
Refrigerant setting:
1=User defined. 3-digits. 2=R22. 3=R134a. 4=R502.
5=R717. 6=R13. 7=R13b1. 8=R23. 9=R500. 10=R503.
11=R114. 12=R142b. 13=User defined. 14=R32.
15=R227. 16=R401A. 17=R507. 18=R402A. 19=R404A.
20=R407C. 21=R407A. 22=R407B. 23=R410A. 24=R170.
25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270.
30=R417A. 31=R422A. 32=R413A. 33=R422D.
34=R427A. 35=R438A. 36=R513A. 37=R407F.
38=R1234ze. 39=R1234yf. 40=R448A. 41=R449A.
42=R452A
1-3* o30 1 1 1 1 1 1 1 1 1 0 42 0
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with
alarm when open. 3=door alarm when open. 4=defrost
start (pulse-signal). 5=ext. main switch 6=night
operation 7=thermostat band changeover (activate
r21). 8=alarm function when closed. 9=alarm function
when open. 10=Appliance cleaning (pulse signal).
11=forced cooling at hot gas defrost). 12=Open night
cover, 13=coordinated defrost).14=Refrigeration
stopped (forced closing). 15=case shutdown. 16=light.
20=Refrigerant alarm. 21= adaptive liquid control
when short-circuited.
1-2* o37 1 1 1 1 1 1 1 1 1 0 21 0
Configuration of light function: 1=Light follows
day /night operation, 2=Light control via data
communication via o39’, 3=The light is controlled
with a door switch on a DI input, 4=As "2", but light
switches on and night cover will open if the network
cuts out for more than 15 minutes. 5=Light controlled
via a DI input.
1-2 o38 1 1 1 1 1 1 1 1 1 5 1
Activation of light relay (only if o38=2) On=light 1-2 o39 1 1 1 1 1 1 1 1 0/O 1/On 0/Off
Rail heat On time during day operations
1-2 o41 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat On time during night operations
1-2 o42 1 1 1 1 1 1 1 1 1 0 % 100 % 100
Rail heat cycle time (On time + Off time) 1-2 o43 1 1 1 1 1 1 1 1 1 1 min. 60 min. 5
Appliance cleaning. 0=no Appliance cleaning. 1=Fans
only. 2=All output Off.
1-2 o46 1 1 1 1 1 1 1 1 1 0 2 0
Selection of wiring diagram. See overview pages 2-4 1-3* o61 1 1 1 1 1 1 1 1 1 1 9 1
Access code 2 (partial access) 2-2 o64 1 1 1 1 1 1 1 1 1 0 999 0
Replace the controller's factory settings with the
present settings
3-3* o67 1 1 1 1 1 1 1 1 1 0/Off 1/On 0/O
Input signal on DI3. Function: (high voltage input)
(0=not used. 1=status on DI2. 2=door function with
alarm when open. 3=door alarm when open. 4=defrost
start (pulse-signal). 5=ext. main switch 6=night
operation. 7=thermostat band changeover (activate
r21). 8=Not used. 9=Not used. 10=Appliance cleaning
(pulse signal). 11=forced cooling at hot gas defrost.
12=Open night cover. 13=Not used. 14=Refrigeration
stopped (forced closing)). 15=case shutdown.
16=light. 20=Refrigerant alarm. 21= adaptive liquid
control when short-circuited.
1-2* o84 1 1 1 1 1 1 1 1 1 0 21 0
Rail heat control
0=not used, 1=pulse control with timer function (o41
and o42), 2=pulse control with dew point functionA
1-2 o85 1 1 1 1 1 1 1 1 1 0 2 0
Dew point value where the rail heat is minimum
1-2 o86 1 1 1 1 1 1 1 1 1 -10°C "o87" 8
Dew point value where the rail heat is 100% on
1-2 o87 1 1 1 1 1 1 1 1 1 "o86" 50 °C 17
Lowest permitted rail heat effect in %
1-2 o88 1 1 1 1 1 1 1 1 1 0 % 100 % 30
Time delay from "open door refrigeration is started
1-2 o89 1 1 1 1 1 1 1 1 1 0 min. 240 min. 30
Fan operation at stopped cooling (forced closing):
0= Stopped (defrost allowed)
1= Running (defrost allowed)
2= Stopped (defrost not allowed)
3= Running (defrost not allowed)
1-2 o90 1 1 1 1 1 1 1 1 1 0 3 1
© Danfoss | DCS (vt) | 2019.07
AN294432763974en-000201 | 13

Other manuals for Danfoss AK-CC55

Related product manuals