AKD 2800
Programming
Minimum reference, Ref
MIN
- Maximum reference,
Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
0-20 mA/ 4-20 mA.
An output signal is obtained, which is proportional to the
feedback value in the interval Minimum feedback, FB
MIN
- Maximum feedback, FB
MAX
(parameter 414/415).
0-f
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
MAX
(parameter
202 Output frequency, high limit, f
MAX
).
0-I
MAX.
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the output current in the interval 0 - I
MAX.
0-P
M,N
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
value set in parameter 102 Motor power, P
M,N
.
0-Temp.
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the present heatsink temperature. 0/4 mA
corresponds to a heatsink temperature of less than
20 °C, and 20 mA corresponds to 100 °C.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -
33